GCM-EC-1207 treatment is an effective corrosion inhibitor for ferrous metals in marine circulating cooling water systems. Because certain aluminum alloys are highly anodic, they may be difficult to completely protect. Therefore, the use of GCM-EC-1207 treatment with systems containing aluminum alloys should be discussed with our representative prior to starting treatment.
In order to ensure the maximum benefits from a GCM-EC-1207 treatment program, the system should be inspected for deposits and corrosion. If the system is found to be contaminated, it must be chemically cleaned before the treatment program begins. Our representative can provide specific cleaning recommendations. Sacrificial anodes (magnesium or zinc) in the cooling system should be removed prior to adding GCM-EC-1207 treatment.
Dosage
The system should be filled with good quality fresh or distilled water and where freeze protection is necessary, the proper amount of glycol-based antifreeze should be added. Begin circulating the system water, and add GCM-EC-1207 cooling water treatment at an initial dosage of 8 liters per ton of system water capacity. Circulate for 30 minutes after addition to ensure good distribution and the establishment of a protective film.
GCM-EC-1207 cooling water treatment may be used with waters that have hardness contamination, provided the total hardness levels are less than 170 ppm or as otherwise recommended by the engine manufacturer, whichever is less. The chloride level in the cooling system should be limited to 100 ppm or as otherwise recommended by the engine manufacturer, whichever is less.